①. 可燃(ran)(ran)氣體(ti)、液化烴(jing)和可燃(ran)(ran)液體(ti)的(de)(de)金屬管道除(chu)規定需(xu)要(yao)采(cai)(cai)用(yong)法(fa)蘭(lan)連(lian)(lian)接(jie)外,均應(ying)采(cai)(cai)用(yong)焊接(jie)連(lian)(lian)接(jie)。公稱直徑等(deng)(deng)于(yu)或小于(yu)25mm的(de)(de)可燃(ran)(ran)氣體(ti)、液化烴(jing)和可燃(ran)(ran)液體(ti)的(de)(de)金屬管道和閥門采(cai)(cai)用(yong)錐管螺紋(wen)連(lian)(lian)接(jie)時,除(chu)能(neng)產生縫隙腐蝕(shi)的(de)(de)介質管道外,應(ying)在螺紋(wen)處采(cai)(cai)用(yong)密封焊。規定采(cai)(cai)用(yong)法(fa)蘭(lan)連(lian)(lian)接(jie)的(de)(de)地(di)方為:與設備(bei)管口法(fa)蘭(lan)的(de)(de)連(lian)(lian)接(jie)、與法(fa)蘭(lan)閥門的(de)(de)連(lian)(lian)接(jie)等(deng)(deng);高黏度、易黏結的(de)(de)聚合淤漿液和懸(xuan)浮液等(deng)(deng)易堵塞的(de)(de)管道;凝固點(dian)高的(de)(de)液狀(zhuang)石蠟(la)、瀝青、硫黃等(deng)(deng)管道;停工檢修需(xu)拆卸(xie)的(de)(de)管道等(deng)(deng)。需(xu)要(yao)經常清掃的(de)(de)分配(pei)主(zhu)管,管的(de)(de)一(yi)端不能(neng)封閉(bi),應(ying)做成能(neng)拆卸(xie)的(de)(de)形(xing)式(shi),見圖2.231。


231.jpg


    管道采用(yong)焊(han)接(jie)(jie)(jie)連(lian)接(jie)(jie)(jie),不(bu)論從強度(du)上、密封(feng)性(xing)能上都是(shi)好(hao)的。但是(shi),等(deng)于(yu)或(huo)小于(yu)DN25的管道,其(qi)焊(han)接(jie)(jie)(jie)強度(du)不(bu)佳且易(yi)將焊(han)渣落入管內引起管道堵塞,因此多采用(yong)承(cheng)插焊(han)管件(jian)連(lian)接(jie)(jie)(jie),也可采用(yong)錐管螺紋(wen)連(lian)接(jie)(jie)(jie)。當采用(yong)錐管螺紋(wen)連(lian)接(jie)(jie)(jie)時,有強腐蝕性(xing)介質(zhi),尤(you)其(qi)是(shi)含HF等(deng)易(yi)產(chan)生縫(feng)隙腐蝕的介質(zhi),不(bu)得在螺紋(wen)連(lian)接(jie)(jie)(jie)處(chu)施以(yi)密封(feng)焊(han),否則(ze)一旦泄(xie)漏(lou),后果嚴(yan)重。


 ②. 可(ke)燃(ran)氣(qi)(qi)體(ti)(ti)、液化(hua)烴(jing)和(he)可(ke)燃(ran)液體(ti)(ti)的管道(dao)(dao)不得穿過與(yu)其無關的建筑(zhu)物。可(ke)燃(ran)氣(qi)(qi)體(ti)(ti)、液化(hua)烴(jing)和(he)可(ke)燃(ran)液體(ti)(ti)的采樣管道(dao)(dao)不應引入化(hua)驗室。


 ③. 可(ke)(ke)燃(ran)(ran)(ran)氣(qi)體(ti)、液化烴和(he)可(ke)(ke)燃(ran)(ran)(ran)液體(ti)的管道(dao)應(ying)架空(kong)或沿地(di)敷設。日(ri)常檢查(cha)、檢修各方(fang)面(mian)都比較方(fang)便(bian),而(er)管溝(gou)和(he)埋地(di)敷設恰好相反,破(po)損不易被及時(shi)發現。必須采用管溝(gou)敷設時(shi),應(ying)采取防止可(ke)(ke)燃(ran)(ran)(ran)氣(qi)體(ti)、液化烴和(he)可(ke)(ke)燃(ran)(ran)(ran)液體(ti)在(zai)管溝(gou)內(nei)積聚的措施,并在(zai)進、出(chu)裝(zhuang)置(zhi)及廠房(fang)處密封隔(ge)(ge)斷;管溝(gou)內(nei)的污水(shui)應(ying)經水(shui)封井(jing)排人生產(chan)污水(shui)管道(dao)。管溝(gou)在(zai)進出(chu)廠房(fang)及裝(zhuang)置(zhi)處應(ying)妥(tuo)善隔(ge)(ge)斷,是為(wei)了阻止火災蔓延(yan)和(he)可(ke)(ke)燃(ran)(ran)(ran)氣(qi)體(ti)或可(ke)(ke)燃(ran)(ran)(ran)液體(ti)流竄。


 ④. 工藝和公用工程管(guan)道共(gong)架多層(ceng)敷(fu)設時,宜(yi)將介(jie)質(zhi)操(cao)作溫度等于(yu)或高于(yu)250℃的(de)(de)管(guan)道布(bu)(bu)置在上層(ceng),液化烴及(ji)腐蝕(shi)性介(jie)質(zhi)管(guan)道布(bu)(bu)置在下(xia)層(ceng);必(bi)須布(bu)(bu)置在下(xia)層(ceng)的(de)(de)介(jie)質(zhi)操(cao)作溫度等于(yu)或高于(yu)250℃的(de)(de)管(guan)道可布(bu)(bu)置在外側,但(dan)不應與(yu)液化烴管(guan)道相鄰。大多數塔(ta)底泵的(de)(de)介(jie)質(zhi)操(cao)作溫度等于(yu)或高于(yu)250℃,當塔(ta)底泵布(bu)(bu)置在管(guan)廊(橋(qiao))下(xia)時,為盡(jin)可能降低塔(ta)的(de)(de)液面(mian)高度,并能滿足泵的(de)(de)有效汽蝕(shi)余量的(de)(de)要求(qiu)。


 ⑤. 氧氣管(guan)道(dao)與(yu)可(ke)燃(ran)氣體、液(ye)化(hua)烴和可(ke)燃(ran)液(ye)體的管(guan)道(dao)共架敷(fu)設時(shi)應布置(zhi)在一側,且平(ping)行布置(zhi)時(shi)凈距(ju)不應小于500mm,交叉布置(zhi)時(shi)凈距(ju)不應小于250mm。氧氣管(guan)道(dao)與(yu)可(ke)燃(ran)氣體、液(ye)化(hua)烴和可(ke)燃(ran)液(ye)體管(guan)道(dao)之間宜(yi)用公用工程管(guan)道(dao)隔(ge)開。


   氧氣管(guan)(guan)道(dao)與(yu)可燃(ran)介(jie)質管(guan)(guan)道(dao)共架敷(fu)設(she)時,兩管(guan)(guan)道(dao)平(ping)行布置的(de)(de)凈(jing)(jing)距為不(bu)小于500mm。但當管(guan)(guan)道(dao)采用焊接連接結構并無閥門時,其平(ping)行布置的(de)(de)凈(jing)(jing)距可取上(shang)述凈(jing)(jing)距的(de)(de)50%,即250mm。


 ⑥. 公(gong)(gong)用(yong)(yong)(yong)(yong)工(gong)程(cheng)(cheng)(cheng)管(guan)(guan)道(dao)在(zai)工(gong)藝裝置中是經常與(yu)可燃(ran)(ran)氣(qi)體(ti)、液(ye)化烴、可燃(ran)(ran)液(ye)體(ti)的(de)設(she)備(bei)和管(guan)(guan)道(dao)相連(lian)接(jie)的(de)。當公(gong)(gong)用(yong)(yong)(yong)(yong)工(gong)程(cheng)(cheng)(cheng)管(guan)(guan)道(dao)壓力因(yin)故(gu)降低時,大量可燃(ran)(ran)液(ye)體(ti)可能倒(dao)流入公(gong)(gong)用(yong)(yong)(yong)(yong)工(gong)程(cheng)(cheng)(cheng)管(guan)(guan)道(dao)內,容(rong)易(yi)引發事故(gu)。如大量可燃(ran)(ran)液(ye)體(ti)倒(dao)流入蒸(zheng)汽管(guan)(guan)道(dao)內,當用(yong)(yong)(yong)(yong)蒸(zheng)汽滅火時起了“火上添油的(de)作用(yong)(yong)(yong)(yong)”。因(yin)此,公(gong)(gong)用(yong)(yong)(yong)(yong)工(gong)程(cheng)(cheng)(cheng)管(guan)(guan)道(dao)與(yu)可燃(ran)(ran)氣(qi)體(ti)、液(ye)化烴和可燃(ran)(ran)液(ye)體(ti)的(de)管(guan)(guan)道(dao)或(huo)設(she)備(bei)連(lian)接(jie)時應符合(he)下列規定(ding):連(lian)續(xu)使用(yong)(yong)(yong)(yong)的(de)公(gong)(gong)用(yong)(yong)(yong)(yong)工(gong)程(cheng)(cheng)(cheng)管(guan)(guan)道(dao)上應設(she)止回(hui)閥(fa)(fa),并在(zai)其根部設(she)切斷閥(fa)(fa);在(zai)間歇使用(yong)(yong)(yong)(yong)的(de)公(gong)(gong)用(yong)(yong)(yong)(yong)工(gong)程(cheng)(cheng)(cheng)管(guan)(guan)道(dao)上應設(she)止回(hui)閥(fa)(fa)和一道(dao)切斷閥(fa)(fa)或(huo)設(she)兩道(dao)切斷閥(fa)(fa),并在(zai)兩切斷閥(fa)(fa)間設(she)檢(jian)查閥(fa)(fa);僅在(zai)設(she)備(bei)停用(yong)(yong)(yong)(yong)時使用(yong)(yong)(yong)(yong)的(de)公(gong)(gong)用(yong)(yong)(yong)(yong)工(gong)程(cheng)(cheng)(cheng)管(guan)(guan)道(dao)應設(she)盲(mang)板或(huo)斷開(kai)。


  止回(hui)閥是重要(yao)的安全設施,但只能防止大量氣體、液體倒流,不能阻止少量泄(xie)漏。


 ⑦. 連續(xu)操(cao)作的(de)(de)可(ke)燃氣(qi)體管(guan)道(dao)的(de)(de)低(di)點應設(she)兩道(dao)排(pai)(pai)(pai)液(ye)閥(fa)(fa)(fa),排(pai)(pai)(pai)出的(de)(de)液(ye)體應排(pai)(pai)(pai)放至密(mi)閉系統;僅在開停工時使用(yong)的(de)(de)排(pai)(pai)(pai)液(ye)閥(fa)(fa)(fa),可(ke)設(she)一(yi)道(dao)閥(fa)(fa)(fa)門(men)(men)(men)(men)并(bing)加絲堵、管(guan)帽、盲(mang)板(ban)或(huo)法蘭蓋。連續(xu)操(cao)作的(de)(de)可(ke)燃氣(qi)體管(guan)道(dao)的(de)(de)低(di)點設(she)兩道(dao)排(pai)(pai)(pai)液(ye)閥(fa)(fa)(fa),第(di)一(yi)道(dao)(靠(kao)近管(guan)道(dao)側)閥(fa)(fa)(fa)門(men)(men)(men)(men)為(wei)常開閥(fa)(fa)(fa),第(di)二道(dao)閥(fa)(fa)(fa)門(men)(men)(men)(men)為(wei)經常操(cao)作閥(fa)(fa)(fa)。當發現第(di)二道(dao)閥(fa)(fa)(fa)門(men)(men)(men)(men)泄漏時,關閉第(di)一(yi)道(dao)閥(fa)(fa)(fa)門(men)(men)(men)(men),更換第(di)二道(dao)閥(fa)(fa)(fa)門(men)(men)(men)(men)。


 ⑧. 甲、乙A類(lei)設(she)備和管道應(ying)有惰(duo)性(xing)(xing)氣體置換設(she)施。甲、乙A類(lei)設(she)備和管道停工時應(ying)用惰(duo)性(xing)(xing)氣體置換,以防(fang)檢修(xiu)動火時發(fa)生火災爆炸(zha)事故。


 ⑨. 當可燃液(ye)(ye)體(ti)容(rong)器(qi)內可能存在空(kong)氣時,其入口管應(ying)從(cong)容(rong)器(qi)下(xia)部接(jie)入;若必須從(cong)上(shang)部接(jie)入,應(ying)延伸至距容(rong)器(qi)底(di)200mm處。從(cong)容(rong)器(qi)上(shang)部向(xiang)下(xia)噴射(she)輸(shu)入容(rong)器(qi)內時,液(ye)(ye)體(ti)可能形成很高的(de)(de)靜(jing)電壓(ya),經測定(ding),汽(qi)油(you)和(he)航空(kong)煤油(you)噴射(she)輸(shu)入形成的(de)(de)靜(jing)電壓(ya)高達數千伏,甚(shen)至在萬伏以上(shang),這(zhe)(zhe)是很危險的(de)(de)。容(rong)器(qi)的(de)(de)任(ren)何接(jie)地都不(bu)能迅速(su)消除這(zhe)(zhe)種液(ye)(ye)體(ti)內部的(de)(de)電荷。


 ⑩. 液化烴設備抽出管道應在靠近設備根部設置切斷閥。容積超過50m3的液化烴設備與其抽出泵的間距小于15m時,該切斷閥應為帶手動功能的遙控閥,遙控閥就地操作按鈕距抽出泵的間距不應小于15m。當與罐直接相連接的下游設備發生火災時,能及時切斷物料。